Rated Voltage 380/400/415VAC 3 Phase+N+PE Voltage Range ยฑ25% Rated Frequency 50/60Hz Auto sensing Frequency Range 40Hz~70Hz Rated Voltage 380/400/415VAC 3Phase+N+PE Rated FrequencyRange ยฑ10% (ยฑ5% Konfigurable) Rated Frequency 50-60Hz Inverter/ Bypass Switch 0ms Output PF 1 Rated Voltage 380/400/415VAC 3PH+N+PE Phase Voltage 220 (200~244V Settable on Display) Crest Factor 3:1 THDu <2%@100% Linear load; <5%@100% Non linear line Voltage Accuracy ยฑ1% Transient Voltage Response ยฑ5%<10ms Overload 125% 10 min; 150% 1 min System Efficiency โฅ93%@100% Load Voltage 360~408V (30-34 units configurable) No netral wire Communication Interface RS232 RS485 optional: dry contact Operating Temperature 40ยฐC Display LCD+LED Touch screen Humidity 0~95% (no condensation) Altitude < 1000m no derating > 1000m derating 1% if every 100 meters increased Noise โค65dB@1m Quality ISO 14001 ISO 9001 ISO 45001 CE Performance IEC 62040-1 IEC 62040-4 EMC/LVD IEC 60601-1 IEC 62040-2 BUILT-IN FEATURES AND SAFETY : AUTHORIZED TECHNICAL ACCESS CONTROL TEMPERATURE WARNING ALARM